|
V.
CRITERIA USED FOR EVALUATING CATHODIC PROTECTION
Criteria
have been developed to determine that a structure has been made completely
cathodic, or in other words that it is fully protected from corrosion.
These criteria are set forth in National Association of Corrosion Engineers
(NACE) Standard RP-01-69 (use latest revision) titled, "Recommended
Practice -- Control of External Corrosion on Underground or Submerged
Metallic Piping Systems." These criteria are also contained in Section
I, Corrosion, of Part 192 (Transportation of Natural and Other Gas by
Pipeline: Minimum Federal Safety Standards), Title 49 of the Code of Federal
Regulations, which was prepared following the passage by the Congress
of the Natural Gas Pipeline Safety Act of 1968.
Probably
the most used criterion is the one based on a simpte measurement of the
electrical potential between the pipeline and adjacent earth or water.
The wording of this criterion is as quoted below from the NACE Standard
RP-01-69:
A
positive indicator for steel and cast iron structures is "A negative
(cathodic) voltage of at least 0.85 voit as measured between the structure
surface and a saturated copper-copper sulphate reference electrode contacting
the electrolyte. Determination of this voltage is to be made with the
protective current applied."
This
is all based on the fact that when a pipeline is under cathodic protection,
direct current flows from the conducting environment onto the pipeline
as shown by Figure 3. This current flow through the environment and coating
resistance forces the pipeline to assume a negative electrical polarity
with respect to the environment. The question, then, is just how negative
the pipe should be to serve as an indication that full protection has
been attained. The value of -0.85 volt is used for steel pipe as measured
using a standard copper-copper sulphate reference electrode to contact
the environment. If other types of reference electrodes are used, the
values will be different.


Figure
4 illustrates how the protective potential is measured. The reference
electrode (used to assure stable and repeatable readings) is normally
placed on the earth surface directly above the pipeline as shown. This
position tends to be a neutral zone where there is the least net
concentration of cathodic protection current flow between the electrode
and the pipe surface. When working with submerged pipelines, suitable
submersion electrodes may be lowered to a position just above the pipeline.
Potentials
on steel pipe which are less negative than -0.85 volt to copper-copper
sulphate electrode indicate less than full cathodic protection. On the
other hand, potentials more negative than -0.85 volt to copper-copper
sulphate electrode indicate wasted energy -- since once corrosion is stopped
at -0.85 volt, there is no real need to carry more negative potentials
at a given point as far as corrosion control at that point is concerned.
In actual practice, however, it is usually necessary to maintain more
negative potentials at drainage points of cathodic protection current
along a pipeline in order to maintain the minimum of -0.85 volt at locations
remote from the drainage points. This is primarily a result of attenuation
-- voltage drops caused by cathodic protection current on the pipeline
flowing through the longitudinal resistance of the pipeline steel in order
to return to the drainage point. In this respect, large diameter coated
lines are much easier to protect cathodically than are small diameter
coated pipes because the larger cross sectional steel area in a large
pipe means lower longitudinal electrical resistance with resulting lower
attenuation.
Where
there are more negative than necessary cathodic protection potentials
on coated pipelines, gaseous hydrogen is generated at coating defects
in the steel surface. Hydrogen bubbles may cause mechanical J lifting
of paint around defects, increasing the current requirements for cathodic
protection. This effect is most likely to occur in environments of iow
resistance.
Avoiding
coating damage by excessive cathodic protection is best accomplished by
avoiding over-protection in the first place although coatings that are
resistant but not immune to this effect can be selected.
Normally,
cathodic protection design engineers will strive to keep the polarization
potential on their protected pipeline below the hydrogen over-voltage
potential, which is the point at which free hydrogen starts to evolve.
The "polarization potential" is the potential measured be* tween
the pipe and adjacent earth immediately (within a fraction of a second)
after cathodic protection current flow to the pipe is interrupted. The
reading must be taken very quickly because the polarization potential
decays very rapidly at first. Although its rate depends upon environmental
conditions, free hydrogen evolution on steel pipe can be looked for when
the polarization potential approaches a value in the order of - 1.2 voit
as measured to a copper-copper sulphate reference electrode.
Other
accepted criteria for steel (and cast iron) structures which may be used
are given below based on the NACE Standard RP-01-69 and are supplemented
by explanatory notes as appropriate.
1) A minimum negative
(cathodic) voltage shift of at least 300 millivolts, produced by the application
of protective current. (Notes: The "voltage shift" is from cathodic
protection current ON to the value read immediately -- within a fraction
of a second -- after turning the cathodic protection current OFF. Does
not apply to ail structures; not applicable to structures in contact with
dissimilar metals. Used where -0.85 volt to copper-copper sulphate electrode
not readily attained. Not always feasible to simultaneously interrupt
all cathodic protection current sources on a protected section of pipeline.)
2)
A minimum negative (cathodic) polarization voltage shift of 100 millivolts
measured between the structure surface and a saturated copper-copper sulfate
reference electrode contacting the electrolyte. (Notes: This is a measurement
of the cathodic protection-OFF decay in the polarization potential. This
decay must be to a point at least 100 millivolts less negative than the
polarization potential measured immediately -- within a fraction of a
second -- after first turning the cathodic protection current OFF. Full
decay may take excessively long on some pipelines. Not always feasible
to simultaneously interrupt all cathodic protection current sources on
a protected section of pipeline.)
3)
A structure-to-electrolyte voltage at least as negative (cathodic) as
that originally established at the beginning of the Tafel segment of the
E-Log-I curve, (Notes: The E-Log-I curve is developed, using specific
techniques, by applying increasing increments of cathodic protection current
to an initially unprotected pipeline and measuring the pipeline.to-reference
electrode potential at each value of applied current. These potentials
are plotted against the logarithm of applied current. Typically, starting
from the minimum applied current value, the plot will appear as initial
and final straight line portions connected by a curved section or "break."
It is the indicated pipeline-to-reference electrode potential at the begining
of the final straight line portion that is used as the criterion of protection.
Effective, but a slow procedure.)
4)
A net protective current from the electrolyte into the structure surface
as measured by an earth current technique applied at predetermined current
discharge (anodic) points of the structure. (Notes: Simplest evidence
of compliance is a definite indication that reference electrodes placed
on each side of the pipeline opposite the previously anodic spot are electrically
positive with respect to a reference electrode placed directly above the
pipeline at the previously-anodic spot, This indicates that direct current
is flowing onto the pipeline from the environment on each side.)
While
the criteria discussed above are the accepted working tools used by pipeline
corrosion engineers to evaluate the effectiveness of their cathodic protection
systems, the ultimate criterion is whether or not the development of pipeline
corrosion leaks has been effectively stopped.
|